UPS Room – Related Fire Code

 IFC 2015, Section 608

Section 608 applies to stationary storage battery systems having an electrolyte capacity of more than 50 gal for flooded lead-acid, nickel-cadmium (Ni-Cd), and VRLA or more than 1,000 lb for Li-ion and lithium-metal-polymer used for facility standby power, emergency power, or UPS.

As defined by IFC 608.6.1, room ventilation:

Ventilation shall be provided in accordance with the International Mechanical Code and the following:

  1. For flooded lead-acid, flooded Ni-Cd, and VRLA batteries, the ventilation system shall be designed to limit the maximum concentration of hydrogen to 1% of the total volume of the room.
  2. Continuous ventilation shall be provided at a rate of not less than 1 cfm/sq ft of floor area of the room.

Exception: Li-ion and lithium-metal-polymer batteries shall not require additional ventilation beyond that which would normally be required for human occupancy of the space in accordance with the International Mechanical Code.

The two ventilation requirements are not an “either/or” permissive option. This is contrary to the requirements of NFPA 1.

Other generic provisions of IFC Section 608 include the following:

  • Must prevent access to unauthorized personnel. This can be accomplished by either locating in separate room or in noncombustible cabinets. They may be located in the same room with the equipment they support.
  • Must provide spill control and neutralization for batteries with free-flowing electrolyte (i.e., flooded cell batteries). No specific threshold is given, but it is assumed to apply where greater than 50 gal. Not required for VRLA or lithium.
  • Must have proper supervision of ventilation system.
  • Must have signage on door.
  • Must have smoke detection.
  • Requires thermal runaway protection for VRLA batteries.
  • Li-ion and lithium-metal batteries don’t require ventilation.

NFPA 1-2015, Chapter 52

NFPA 1 is not as frequently adopted by municipalities as the IFC. While the basic requirements of NFPA 1 generally parallel those of the IFC, the technical provisions within NFPA 1 do have significant difference that can impacted the design of related battery ventilation systems. These requirements are as follows:

Chapter 52 applies to stationary storage battery systems having an electrolyte capacity of more than 100 gal in sprinklered buildings or 50 gal in nonsprinklered buildings for flooded lead-acid, Ni-Cd, and VRLA batteries or 1,000 lbs for Li-ion and lithium-metal-polymer batteries used for facility standby power, emergency power, or UPS. This is a significantly lower threshold than that in IFC.

NFPA 1, 52.3.6 Ventilation indicates:

For flooded lead-acid, flooded Ni-Cd, and VRLA batteries, ventilation shall be provided for rooms and cabinets in accordance with the International Mechanical Code and one of the following:

  1. The ventilation system shall be designed to limit the maximum concentration of hydrogen to 1% of the total volume of the room during the worst-case event of simultaneous “boost” charging of all the batteries in accordance with nationally recognized standards.
  2. Continuous ventilation shall be provided at a rate of not less than 1 cfm/sq ft of floor area of the room or cabinet.

This language allows for significantly more flexibility than IFC. Other provisions of Chapter 52 include the following, which are not addressed in the IFC:

  • In assembly, educational, detention, health care, day care, etc., battery systems shall be located in a room separate from other portions of the building and be 2-hour fire-rated.
  • Thermal runaway protection is required for lithium batteries.
  • Spill control is required where there are more than 55 gal in individual vessels or an aggregate capacity of greater than 1,000 gal.
  • The battery environment shall be controlled or analyzed to maintain temperatures in a safe operating range for the specific battery technology used. In the case of VRLA batteries, they’re typically rated for an ambient of 77˚F. Although it is not specifically stated, this effectively requires that air conditioning be provided for most battery rooms.

Lithium Ion Battery Fire Video

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out /  Change )

Google+ photo

You are commenting using your Google+ account. Log Out /  Change )

Twitter picture

You are commenting using your Twitter account. Log Out /  Change )

Facebook photo

You are commenting using your Facebook account. Log Out /  Change )

Connecting to %s